Hours of Operation:
Monday to Friday:
8:00 am to 5:00 pm Pacific

Contact Info:
TEL. 604.732.0142
FAX. 604.737.0162
EMAIL: sales@retrotec.com

Testing Enclosures : Sealing Rooms for Clean Agents

This bulletin has been prepared to assist anyone who must seal a room for a Clean Agent
system. Obviously, if a Clean Agent concentration test is to be run, the room will need to
be tight to pass that test. Even so, if no concentration test is required, the room will still
need to be sealed. It is the nature of Clean Agent that it will suppress all flame and fire
spread but it cannot in every instance extinguish the initial source of ignition (for instance,
severe electrical short circuit). Therefore it is critical that the Clean Agent remain in the
protected area until emergency personnel have a chance to deal with a possible continuing
source of ignition.

  1. ALL DOORS leading from the Clean Agent protected areas or into another Clean Agent
    zone shall have drop seals on the bottoms, weather stripping around the jams,
    latching mechanisms and door closer hardware. In addition, double doors shall have a
    weather stripped astragal to prevent leakage between doors and a coordinator to
    assure proper sequence of closure. In general, doors shall be treated as though they
    are being weatherproofed for outside use with the least amount of light possible
    passing around all sides. Doors, which for any reason cannot be kept normally closed,
    should be equipped with electromagnets designed to release on alarm.
  2. ALL DUCT WORK leading from or into a protected area may be permanently sealed
    off, air tight, with metal plates caulked and screwed in place. Ductwork left in
    service from the building air handling unit must have butterfly blade type dampers
    installed with neoprene seals. Dampers must be spring loaded or motor operated to
    provide 100% air shut-off. It is further recommended that the building air handling
    units be shut down to prevent the spread of smoke or Clean Agent into other areas of
    the building.
  3. SELF-CONTAINED AIR HANDLING UNITS within the protected zone may be left in
    service at the owner's option. However, one must consider the possibility that the air
    handling unit could be the source of the fire. Systems not manned 24 hours a day
    should be tied-in to shutdown.
  4. PROTECTED AREAS should be enclosed with wall partitions which extend slab-to-slab.
    In areas where this is not possible, the ceiling tiles should be clipped. If the ceiling
    rests on top of the walls, all tiles should be clipped and a caulk be applied around the
    entire perimeter where tile touched the walls. In either case, all tiles should be
    clipped in place within 4 feet of any discharge nozzle.
  5. ANY HOLES, CRACKS, OR PENETRATION leading into or out of the protected area must
    be sealed. This includes pipe chases and wire troughs.
    All walls should be caulked around the inside perimeter of the room where the walls
    rest on the floor slab and where the walls intersect with the ceiling slab above.
  6. IF A RAISED FLOOR continues out of the Clean Agent protected area into adjoining
    rooms, bulkheads must be installed under the floor, directly under above-floor border
    partitions. These bulkheads must be caulked top and bottom.
    If the adjoining rooms share the same under-floor air handlers, then the bulkheads
    must have dampers installed the same as required for ductwork. See Item #2.
  7. ALL FLOOR DRAINS should have traps and the traps should be designed to have water
    in them at all times.
  8. POROUS BLOCK WALLS must be sealed slab-to-slab to prevent gas from passing
    through the block. Two or three coats of paint are normally required. Unpainted
    block walls are totally unacceptable.
  9. IN GENERAL, the basic intent is to make Clean Agent protected areas as air tight as
    possible during and after Clean Agent discharge. Clean Agent is heavier than air and
    therefore, openings below floors are usually more critical than those above a ceiling.
    However, during discharge the room does get pressurized to some extent and any gas
    that can be pushed out of the room will not return. Smaller rooms are much harder
    to seal then large rooms because each little crack becomes much more significant as
    the surface area to volume ratio changes.
  10. ONCE THE GAS IS DISCHARGED, in most jurisdictions, it must remain in the room at
    it’s designed concentration at least ten minutes. The length of time the agent will
    remain is directly proportional to the “air tightness” of the room..

The above 10 points are not all inclusive nor guarantee that the concentration test will pass.
They are, however, presented as the most common items which affect Clean Agent
concentration tests. If, in addition to presenting a few specific areas of concern, they
provoke thought about the overall "air tightness" of the enclosure, then they will have served
a good purpose.

Specialized air sealing materials

Hire contractors who are familiar with airsealing, not unspecialized contractors.

Airseal ManufacturerContactPhone
3M for spray sealwww.3M.com
W.R.Grace for spray sealwww.Grace.com(800)334-8796
GE SiliconesCustomer Development(800)255-8886
O-Z/GedneyPatsy Sanders(918)627-5530
TremcoFrank Calabrese(206)252-3372
Thermal Ceramics Inc(404)796-4280
3MTodd Regenold(415)563-5992
Flame Stop IncJames Bower(817)431-3747
True North Technologies(416)744-2233
Unifrax Inc/Carborundum Fibers DivisionSarah Brewer(716)278-2203
International Protective Coatings Corp(800)334-8796
Dow Corning Corporation(517)496-4000
Specified Technologies Inc(800)992-1180
Thermafiber(800)426-8127