Duct Testing Systems : Q32 Duc-Tester

Automated Duct Testing without a computer…for measuring duct leakage in residential & light commercial buildings.

Retrotec Model Q32 consists of a Duc-Tester Module, a DM-2A Digital gauge and a 12 foot flex-duct with flanges for mounting on the return register. Click on the desired test pressure and walk away; the DM-2A will run the test for you. Case for DM-2A and grill mask dispenser not included.

DM-2A adjusts speed and measures duct leakage automatically.

The DU220 fan unit has three flow ranges.

New Home or Utility Standards

The Retrotec Duc-Tester is designed specifically to measure residential duct leakage. It can then be used to locate duct leaks and to measure the results of duct sealing. Use the Model Q32 Duc-Tester to verify duct leakage for compliance with codes such as Title 24 in California. The typical 5 Ton air-conditioning system must have 120 cfm of leakage or less to pass California standards. The Q32 will easily test any residential system because it will create 600 cfm which is 5 times more than that.

Fan Flow (accuracy +/- 2.5 % with Retrotec DM-2 or Auto Correct software)

Maximum Flow in Free Air750 CFM353 l/s1273 m3/h
Maximum Flow at 25 Pascal with flex attached to a register530 CFM250 l/s901 m3/h
Minimum Flow at 25 Pascal test pressure with flex attached5 CFM2.36 l/s8.49 m3/h
Dimensions of Fan Unit14 × 14 × 12 in (35 × 35 × 30 cm)
Fan Motor: EBM backward curved impeller120V 2a or 240V 1a
Dimensions of Flex Duct10” diameter. 15” to 10’ in length.
Dimensions of Carrying Case25” × 14” × 15”

Calibration meets: Canadian CGSB-149.1-2002 & SuperE, USA ASTM E 779 – 03, European EN 13829 & CEN, UK TM-23 Energy Standards. NFPA 2001- 01, ISO 14520 and fire standards.

Specifications subject to change without notice. Infiltrometer is a registered trademark of Retrotec. Two (2) years parts and labor on fan unit

Operation

The Duc-Tester will pressurize or depressurize a duct system (with the air handler off) from the main return grille (or blower access opening). The rest of the register openings are taped shut. Duct pressure is measured by static probes in the supply ducts. Airflow is determined by reading flow directly from the DM-2. No computer is required. Setup, taping the registers and getting results takes less than 20 minutes in most homes. The Duc-Tester can also be used in conjunction with a blower door to neutralize duct leaks to indoors to that only duct leakage to outdoors is measured.

Q32 Duc-Tester Photographs


The DU220 fan has 3 flow ranges.


The built in computer on board the DU220 fan allows for automatic control.